Tip:
Highlight text to annotate it
X
PBM Demo Equipment - Motor Management System
PBM Demo Equipment is a system for engine protection
that allows us
to perform functional tests on a Fanox relay
generating various faults in the engine
For these probes we have
the relay protection Fanox PBM B
the display module PBM H
different systems for generating fouls
an engine
and a brake
PBM B includes
auxiliary voltage terminals
reset input terminals
toroidal transformer voltage terminals
PTC terminals
output relay for tripping
output relay for alarm
communication terminals
reset button
and alarm signalling leds
el disparo y alarmas
RJ45 connector for to PBM H display or PC
PBM H display
consists on a display
6 configurable leds
and 9 keys for navigation
Through the switches and buttons we can generate different failure conditions
that will be detected by the relay in order to protect the engine
The reasons of failure that we can generate will be
overload
phase unbalance fault
short-circuits of the PTC probe
over temperature
by PTC probe
and differential ground fault
Trip times
may be controlled by the timer
The PBM demo equipment has a real engine
to perform all tests
as well as a brake to prove faults at JAM or locked rotor
The first step will be to define the General settings of the engine
that we want to protect
The general settings
will be
a rated current of 0.8 amp
current transformer ratio of 1 in order that the passage of the cables
is direct through the relay
the line frequency is 50 Hz
the limit of the engine start is 1.5 amps
In this case, we have set engine starting time at 0 seconds
This way the relay will consider that the engine is started in the initial conditions
and the sequence of phases
is A-B-C in direct sequence
Overload
The first fault that we are going to generate is a failure by overload
We start the engine at rated conditions
the motor will start running
and then generate. We will create an overload that will increase
the current drawn by the motor
also the thermal memory
will increase gradually
tripping the alarm over the 40% of the value which is the set value
and when the thermal memory reaches 100%, the relay shall deem that
the engine is excessively hot and stop it
The overload preset functions are:
permit of the function which in this case is enabled
tripping value
that is adjusted to a 1.15 times
of the rated current
trip class in this case class 5
automatic ventilation
that we don´t have it
and overload signaling alarm, in this case at 40%.
We start the engine at rated conditions
and we can see in the measures section the consumption of it
in this case 0.8 amps approximately
We can see that the thermal memory increases progressively
until reaching a point of equilibrium
In case of generating an overload
thermal memory increases much more quickly
due to the motor consumption
which has increased almost to double
When the alarm has exceeded
the 40%
LED alarm indicator has been switched on
thermal memory will increase until rising
up to the value of 100%
which represents
an excessively hot state of the engine
and the relay will stop it
As soon as thermal memory has about reached 100% of its value
As soon as thermal memory has about reached 100% of its value
the relay has considered that the engine was too hot
and should be protected and stopped
the thermal memory will start to descend
representing the cooling cycle of the engine
and will allow reconnecting the engine
when its value has fallen below the adjusted alarm value
in this case 40%
Once engine starts
there is power consumption again so the thermal image starts increasing again
If we remove
the overload fault
thermal image rises progressively to a point of
equilibrium placed around 69% of its value
In rated conditions
the relay considers that the engine is in a point of stable temperature
and it will continue operating without interruption
When the thermal image reaches this point of equilibrium, the value remains constant
Phase Loss
Next engine fault that we are going to generate is a phase loss
Phase loss function settings are the following ones:
Permit of the function which in this case is enabled
the percentage of unbalance
set to a value of 30%
if the let-through current is less than 30% of the set value, PBM will consider that
there is a phase loss
and finally the trip time, in this case, set to 5 seconds
We start the engine at rated conditions
and we see that the current consumption is 0.77 Ampere
If we generate a phase loss in phase A
the current consumption disappears
and the relay stops the engine once the 5 seconds
that we have adjusted for tripping have passed
The relay is set in such a way
that it performs an automatic reset
after 5 seconds
If the reason of absence continues
it attempts to protect the engine again
If the reason of absence disappears
the engine will continue running without interruption
Over temperature by PTC
We will generate a trip caused by an over temperature PTC probe
The PTC function settings
are only
the permit of the function
We start the engine at rated conditions
and we generate a fault by PTC probe
PTC´s probe trip is instantaneous
and will not be reset until the failure has gone
As long as the fault remains
the relay will not attempt again to start the engine
Once the fault is gone
after 5 seconds the relay attempts again to start the engine
PTC-s short-circuit
If there is a
malfunction of the probe
being in short circuit for example
the relay will consider that the engine can continue operating
but it will need maintenance work
This will be indicated
by a flashing
of the led
We have the indication
in the leds
and in the display as well
Entering the PTC
probe status menu
we see that there is no over temperature fault
but there is an alarm switched on due to a short circuit of the probe
If the short circuit disappears
or if it is repaired by maintenance personnel
the status of the short circuited probe
turns off
and it will simply need a reset
of the cause of signalling
Defined time differential earth fault
The next fault that we are going to generate will be a differential earth fault in this case
with defined and fixed trip time
The function settings are:
Permit of the function which in this case is enabled
tripping tap set to 100 miliamperes
and operation time adjusted to 0.2 seconds time
We start the engine at rated conditions
and using this button we will generate a differential earth fault
The relay
will stop the engine
and once it detects that the fault has disappeared
allows resetting it without interruption
If the fault keeps on
when try to start the engine
PBM-B will trip again
If the fault disappears
the engine restart happens in a normal way
Locked rotor
The last fault that we are going to generate will be a locked rotor
Locked rotor function settings are:
Permit of the function
which in this case is enabled
trip tap
set to 3.5 times
the rated current
and trip operation time set to 5 seconds
Firstly
we will activate the engines brake
which will generate a locked rotor
We start the engine
and after 5 seconds
the relay stops the engine to protect it
After 5 seconds it will try again to restart the engine
The fault hasn´t disappeared so
the relay will trip again
If we release the engine brake
the relay will allow the starting of the engine
and it will work in an uninterrupted way
These devices protect and control the engines of the greater biomass power plant of Spain in San Juan el Puerto (Huelva)
For more specific information in english visit www.fanox.com