Tip:
Highlight text to annotate it
X
Last few classes we were discussing about biological processes for water and wastewater
treatment. We have seen that how the biological processes are working and how the organic
matter whatever present in
the water and wastewater is getting removed by the microorganisms and we have seen in
detail what is an activated sludge process and what are the process modifications. We
also discussed about the excess
sludge production and what is the loading rate we can adapt for the activated sludge
process. We have seen about what type of a process we have to adopt for a particular
type of wastewater.
For example, if the wastewater is having colloidal particles and rich in organic matter then
it is always advisable to go for contact stabilization tank and for small communities we prefer to
have extended aeration
system or oxidation ditches. So today we will see what is the oxygen requirement in an activated
sludge process or in any aerobic process and what is the nutrient requirement for the microorganisms
and other
factors which affect the biological processes.
Why oxygen is required in a biological process? The process itself is like that. The microorganisms
are utilizing the organic matter whatever is present in the wastewater so because of
the air supply the organic matter is getting oxidized to carbon dioxide and
water and more and more new cells will be generated. So the oxygen requirement or the
oxygen consumption rate is much more than whatever can be got by natural replenation
because the system is open to the
atmosphere so definitely natural oxygen transfer will be taking place from the atmosphere to
the wastewater or the treatment system. but that oxygen transfer is very very less compared
to the oxygen requirement
in any system.
How can we supply this oxygen? We have to supply externally or by some mechanical
means we have to supply the oxygen. Thus, if you want to design any mechanical system
for the oxygen supply or oxygen transfer we should be able to tell
what is the oxygen requirement per unit time in the system. How can we find out that oxygen
requirement? We can find out the total oxygen requirement by using this formula; q into
BOD influent minus BOD
effluent. BOD is nothing but the biochemical oxygen requirement. So if you know what is
the influent BOD and what is the effluent BOD so whatever is the difference between
the influent and effluent that will be
consumed or that much oxygen is consumed during the process. So we have to supply that much
of oxygen. q is the flow rate. That means this much of meter cube of water per day or
per hour is coming to the
system.
We also discussed that in any microbial system there are two processes. One is catabolism
and another one is anabolism. In catabolism what will happen is the microorganisms will
be utilizing the organic matter
and that organic matter will be undergoing a series of oxidation reduction reactions
and the energy will be liberated. This energy will be utilized for the cell maintenance
or the energy liberating reactions of the cell
that is known as catabolism and anabolism is the one which utilizes the organic matter
or the carbon available in the waste and the microorganisms will be creation or generating
or synthesizing new cells.
The energy required for this one is coming from the catabolism process because of a series
of oxidation reduction reactions. Or in the substrate level oxidation reduction so much
of energy will be liberated and
this energy will be stored in the cells in the form of ATPS. And by hydrolysis of this
ATP the energy will be liberated and this energy will be utilizing for the cell synthesis.
So any microbial process we will be
having this catabolism and anabolism. Because of the anabolism more cells will be synthesized.
Therefore, when we talk about the oxygen requirement the organic matter whatever is getting converted
to new cells will not be getting oxidized so, for that one oxygen is not required. How
can we find out the
total oxygen requirements in an activated sludge process? We can find out what is the
net biomass production in the system. At steady state we assume that net biomass production
in the system is zero that
means amount of biomass synthesized for the given amount of time is equal to amount of
biomass wasted from the system. That is the steady state condition.
Oxygen is not required for that part of substrate which form the biomass because that is not
undergoing any further oxidation, it will be getting more complex and the biomass will
be generated. So how can we
find out what is the portion of the organic matter that is going for cell synthesis. That
we can get from the yield coefficient. Yield coefficient is nothing but per unit substrate
consumption, what is the biomass
yield that is the yield coefficient.
We know that some portion of the organic matter is going to be used for the cell synthesis.
How can we find out, what is the oxygen that is not required for this cell synthesis? We
were told that the oxygen
requirement is nothing but q into BOD influent minus BOD effluent. From that one we have
to detect this portion whatever is going for the cell synthesis? So, for that one we have
to find out what is the general
formula of a cell and from that one we can find out what is the oxygen required for the
complete oxidization that organic compound and if we know that, that much is going as
cell we can detect that amount
exactly from the oxygen requirement if the entire system is going to get oxidized. So
the empirical formula for biomass is reported like this; C5H7NO2. So how can we get this
one this is based upon the CHNO
analyzer, Carbon Hydrogen Nitrogen Oxygen analyzer.
So you take the cell or the biomass and analyze for what is the percentage of carbon present,
hydrogen present, nitrogen present and oxygen present using the CHNO analyzer then we can
make an empirical
formula. This is the simplest formula available for a biomass C5H7NO2. But this is not very
commonly used because we know that phosphorus is a high essential element for the microbial
cell. In this formula
there is no phosphorus available. So the most commonly used formula is this one; C60H87O23N12
and P. That means one biomass cell or one microbial cell will be having 60 carbon molecules,
87 hydrogen
atoms, 23 oxygen, 12 nitrogen atoms and 1 phosphorus.
So, if you take the simple formula for the microbial cell that means C5H7NO2. You can
find out what is the total oxygen required for the oxidation of the cell because we have
incorporated this oxygen
requirement also in the initial formula that means q into BOD of the influent minus BOD
of the effluent. So if we can find out what is the oxygen required for the complete oxidation
of this one that much we can
detect from the initial value then we will be getting the total oxygen requirement in
the system.
So if you want to find out what is the total oxygen required for a complete oxidation of
the system what we have to do is we have to convert carbon completely to carbon dioxide,
hydrogen to water, nitrogen to
either ammonia if we are stopping at the carbonaceous stage. But if you want to go for complete
oxidation that ammonia has to be taken or converted to nitrate. So this will be the
final formula; C5H7NO2 plus
5O2 will be giving five carbon dioxide plus 2H2O plus ammonia. Here we are considering
only up to this stage we are not going for the nitrification. So if you see this one
around 1.42 units of oxygen is required
per unit biomass oxidized.
If you take the molecular weight of this one this is equivalent to 5 into 32 so from this
one we can find out around 1.42 unit of oxygen is required per unit biomass oxidized.
So in any system if you want to find out the net oxygen requirement that is equal to total
oxygen required minus 1.42 times total biomass present in the system. In the last class we
saw what is the total biomass
produced in the system so delta O2 means the oxygen requirement in the system is nothing
but q into S0 minus Se S0 is the initial BOD; Se is the effluent BOD minus 1.42 times delta
x. Or this one we can write
again this; q into S0 minus Se minus 1.42 into y observed which is the observed yield
coefficient.
That means total yield coefficient is there, we are taking care of the decay part so that
will be the observed yield coefficient. So, y observed into q into S0 minus Se. Or we
can write in another way; delta O2 is
equal to q into S0 minus Se into 1 minus 1.42 y. So we take it as yt plus 1.42 into kd into
va into x plus NOD. So this formula shows we are considering the y total here. That
means what is the actual yield
coefficient plus this one again we are taking because kd into vax is the amount of biomass
that is undergoing decay or endogenous respiration. That means the biomass is getting oxidized.
So the same formula
whatever we have seen earlier we can use the same thing.
If we want to oxidize the particular amount of biomass then we have to supply 1.42 units
of oxygen per unit of biomass that is why this is coming like this and NOD is nitrogenous
oxygen demand. Nitrogenous
oxygen demand is ammonia. When ammonia is oxidized in the presence of certain microorganisms
then the final end product will be nitrate. So, for that one if you have one unit of ammonia
we need 4.57 units of
oxygen. This we will see in detail when we talk about nitrification and denitrification.
We will be seeing in detail about what is the nitrogenous oxygen demand.
The total oxygen demand is nothing but q into S0 minus Se into 1 minus 1.42 yt this is the
total yield coefficient plus 1.42 kd vax kd is the decay coefficient plus NOD. NOD is
the nitrogenous oxygen demand,
and TKNo is nothing but the total Kjedahl Nitrogen in the effluent which is expressed
in terms of milligram per litter as nitrogen. So if you know the total nitrogen present
in the system and total BOD that means
influent BOD effluent BOD and if you know the bio kinetic parameters like yt and kd
we can find out the total oxygen requirement.
Whenever we go for any aerated design that aerator should be able to supply this much
of oxygen to the system at any time that is the basic design criteria. Now we will see
that any biological system for the
growth of microorganisms should have nutrients. We should supply enough nutrients to the system
because in the empirical microbial formula itself we have seen that carbon is present,
nitrogen is present,
oxygen is present and apart from that one nitrogen and phosphorus are there. And if
you take the biomass and if you burn it we will be getting around 6 to 14% ash. This
ash mainly contains phosphorus,
sodium, potassium, calcium etc or chloride because all these nutrients or all these elements
are present in micro or macro quantities in microorganisms.
So if the microorganisms have to grow properly we have to supply these nutrients that are
adequate for the cell growth. And whenever we take the microorganism or the sludge if
you burn it all the carbon will be
converted to carbon dioxide nitrogen will be converted to nitrogen gas and hydrogen
converted to H2O so the remaining ash whatever is present is the micro and macro nutrients
present in the system.
How can we find out what is the nutrient requirement in the system?
Here also we have to use the empirical formula for the microbial system. The most widely
use molecular formula as we have already seen is C60H87O23N12P. So if you find out the molecular
weight of this one
that means 60 into 12 plus 87 into 1 plus 23 into 6 plus 12 into 14 plus phosphorus
we will be getting 1374. The molecular weight of this compound is 1374 grams. And if you
want to find out what is the nitrogen
fraction it is nothing but 14 into 12. So nitrogen fraction we can find out 14 into
12 divided by the total molecular weight that means 0.122. That means if you take 1 gram
of the biomass it will be containing 0.122
grams of nitrogen.
That means if you want to generate cells in the system apart from carbon and hydrogen
and oxygen we are supplying anyway we have to supply enough nitrogen and phosphorus to
the system otherwise the cell
growth will not be proper or cell growth will not be taking place. So if the wastewater
is not having the nitrogen we have to supply nitrogen in this ratio. That means per gram
of biomass generated we have to
supply 0.122 grams of nitrogen or nitrogen requirement for the entire system is equal
to 0.122 into the total biomass that is going to generate in the system.
Similarly we can find out what is the phosphorus requirement. So here we can take the molecular
weight of phosphorus divided by 1374 we will be getting 0.023 and total phosphorus requirement
is nothing but
0.023 into delta x because delta x is the entire biomass that is going to be generated
in the system. So, whether the nutrient requirement in a system is always a constant? It is not.
Whether we have to supply these
nutrients externally all the time? The answer is no because whenever we talk about the wastewater
especially the domestic wastewater it will be containing lot of nitrogen and phosphorus
most of the times in
excess of the requirement of the microorganisms so we do not have to supply any nitrogen or
phosphorus to the system.
But whenever we go for industrial wastewater treatment especially the system which does
not have any nitrogen or phosphorus we have to supply nitrogen and phosphorus externally,
that is why the ratio is very
very important. We have seen that the ratio is 0.122 and 0.023 and we should know whether
it remains constant in a particular system, most of the time it will not remain as a constant
because it is a function of
the biological sludge retention time. When we were discussing about the process modification
of activated sludge process we have seen that in certain systems the cell generation or
the net cell production is very
very minimal. But in certain other system the cell generation is very high.
For example, in high rate activated sludge process the cell generation is so high. More
than 50% of the organic matter whatever we are supplying to the system is getting converted
as microbial cells. But when we
talk about extended aeration system the net cell production is zero or the mu of the specific
growth rate of the system is zero. That means the net production is zero, ultimately no
microorganisms is generated in
the system.
If there is no microorganism generation in the system naturally the nutrient requirement
will be almost zero because whatever nutrient is available in the system initially the microorganisms
will be utilizing them for
the synthesis of the cells and those cells whatever is generated will be undergoing auto
oxidation and again the nutrients will be released to the system and for the new cells
synthesis the same nutrients will be
available. So the net nutrient requirement for the system will be 0. That is what this
graph shows.
How the nitrogen phosphorus and BOD ratio changes with respect to the biological sludge
retention time? As the biological sludge retention time increases
we can see here BOD is to nitrogen is to phosphorus ratio also increases. If the BSRT is very
very low that means just like a high rate activated sludge process the
BOD is to nitrogen is to phosphorus ratio is 50 is to 5.4 is to 1 that means we have
to supply more nitrogen and phosphorus compared to the BOD. But as the BSRT increase we can
see that it is coming to 100
is to 5.4 is to 1 then 150 is to 5.4 is to 1 and 200 is to 5.4 is to 1. So depending
upon the process modification or depending upon the nature of the process we are choosing,
the nutrient requirement also will
change. So when we talk about the nutrient requirement and the nutrient present in the
system depending upon the requirement we can select the process according to our convenience.
What I mean is, if some
industrial wastewater is there and there is not sufficient nutrient present in the system
and external addition of this nutrient is costly so we can go for a system which requires
least nutrients that means extended
aeration system. So, depending upon the nutrient availability and the requirement we can make
the choice according to our convenience. Now we will talk about the solid liquid separate
process in activated
sludge process.
We have seen that in an activated sludge process unless the solid liquid separation is there
we cannot call it as treatment process because in aeration tank only the conversion of soluble
cod or soluble BOD to
colloidal solids or colloidal BOD is taking place. Because the organic matter whatever
is present in the system is getting converted to new microbial cells and that new cells
will be remaining in the system. So, if
you take the BOD of the sample from the aeration tank it will be almost same as that of the
influent.
Some reduction will be there because whatever is getting oxidized for the catabolism process
whatever is converting to carbon dioxide and water during the catabolism process that much
of reduction will be
there in the BOD. But whatever is converted into a cell will be remaining the system and
that will be contributing to the BOD. So if you not have a sedimentation tank after the
aeration tank your treatment
efficiency will be very very less in an activated sludge process. So, solid liquid separation
process is very very essential in an activated sludge process.
We have seen that the microbial growth stage is also important for this solid liquid separation
process. Because if the microorganisms are in the low growth phase what will happen is
they will be staying as
discrete particles or the flocculation of the particle is almost impossible. But if
they come to the stationary phase or endogenous respiration phase or the end of the stationary
phase the microorganisms start
secreting or producing extra cellular polymers that will be acting as natural biopolymers
which enhances the flocculation of the system or flocculation of the microbial cells. Once
the flocculation take place then it
is very easy for the solid liquid separation process.
Now we will see in detail on how we can design a solid liquid separation system for an activated
sludge process. When we come to the sedimentation tank design of for an activated sludge process
or the
secondary sedimentation tank design we have to meet two criteria; one is to produce clear
effluent to meet the effluent discharge standard, the second one is to concentrate the biological
solids to minimize the
quantity of sludge that must be handled.
So whenever we go for design these two objectives should be satisfied. So how can we satisfy
these two objectives? The tarification is based upon how fast the particles are settling
but the thickening is entirely
different from that one because it will be settling but if the settled sludge volume
is very high then the sludge handling will be so difficult. Moreover, whatever sludge
is generated in the activated sludge process it
is active biomass so we cannot discharge them into the sludge drying beds but we have to
go for further treatment which can stabilize the sludge. Therefore it is always advisable
to have the minimum volume of
the sludge then we can reduce the volume of the sludge digester or any further treatment
whatever we are proposing to take care of the sludge.
Now we will see in detail how can we go for the design of the secondary sedimentation
tank to meet these two objectives that means clarification as well as sludge thickening.
In the initial classes we discussed
that the settling can be classified into four different categories; one is type one settling,
second one is type two settling, the zone settling and compression settling. So whenever
we talk about the secondary
sedimentation tank of an activated sludge processes the sedimentation tank or the settling
is coming under zone settling and compression settling.
Zone settling is taking place when we talk about the clarification and compression settling
is coming into picture when we talk about the sludge thickening. Here zone settling
is taking place because the particles
whatever is present or whatever is coming to the secondary sedimentation tank is flocculent
in nature. And if you see the concentration of the particle it is very high. We discussed
already that the MLSS
concentration in a conventional activated sludge process varies from two thousand to
five thousand milligram per liter so the concentration of the suspension is relatively high and the
particles are flocculent in
nature.
• Biomass concentration varies from 2000 to 5000 milligram per liter
• Flocculent in nature • Concentrated suspension of flocculent
particles • It is coming under type 3 or Zone Settling
How can we go about for the design? Here also we have to conduct the batch analysis.
How can we conduct the batch analysis? The batch analysis can be conducted in measuring
cylinders or small settling column. This is the settling column so what we have to do
is first fill the settling column with the sludge which is having the same
concentration as that of the activated sludge process say two thousand to five thousand
milligram per liter. Hence, the sludge we are taking here and this is the time so what
we have to do after that is with respect
to the time find out what is the position of this sludge.
So we will be observing different zones in the settling. This is the air portion this
is the clarified zone and another zone will be there which will always maintain the same
concentration of the sludge whatever we
have introduced in the first column and we will be having a compression or thickening
zone here and the bottom most portion is the compression zone.
So with respect to time we have to find out what is the depth of this clarified zone.
That means we will be having a very clear zone as well as a zone which is having the
same thickness of the particles as we have
introduced. So we will be taking the depth of the clarified zone with respect to time
till there is no increase in the depth or there is no increase in the depth of the clarified
zone. So here it is very very clear. This is
the initial stage when the initial concentration of the particle is equal to C0.
After time T1 the clarified zone is coming out up to here and entire sludge is settling
as a blanket that is why it is known as zone settling. So the clarified zone is coming
up to here so we know what is the height
of the clarified zone then at T2 again we are taking the height of the clarified zone
and like that we are going on and after sometime we can see that this depth is not increasing
considerably or the curve is
becoming almost flat so this information we can use for the design of the clariflocculator.
That means this portion this clarified zone represents how we can get the clear effluent
from the settling tank and this portion will tell us how much concentrated sludge we can
produce using the settling column
or using the sedimentation tank because we are using the same data for the design of
the sedimentation tank so it will be able to tell us what is the effluent quality or
what is the area required for getting the effluent
quality and what is the area required for getting the desired sludge concentration.
Now let us go into the detail of the analysis.
I have already discussed about the different zones visible in the settling column analyses.
A is the clarified zone; B is the zone where initial concentration C0 is preserved. That
means always the same concentration will be there and C is the thickening zone and D is
the compression zone.
Therefore if you put different concentrations of the sludge in the settling column because
as I have told you whatever sedimentation tank we have to design we have to take the
same sludge concentration of that
in the aeration tank for which we are going to design the sedimentation tank. We have
seen that the sludge concentration can vary from two thousand to five thousand. So what
will happen if the sludge
concentration varies? The settling column experiments or the curve's nature will be
something like this if the concentration is very low the initial settling will be very
fast so we will be getting a curve something
like this and as the concentration increases the curve will be coming like this.
Here we can see C4, this is having maximum concentration and C1 is having the least concentration.
So if the sludge is having less concentration the clarification will be very very fast because
this is the slope that
gives the settling velocity of the particle. Now if you have the settling column analysis
data, and since we will be doing the experiment with a particular concentration finally we
will be getting a curve something like
this and this is the portion where the compression is taking place and it will be becoming asymptotic
to the x axis. So what we have to do is draw tangents to this straight line portion and
this asymptotic portion.
That will be acting at a point say here O.
Here the O point is coming by drawing tangents to the top portion where it is a straight
line and draw a tangent to this portion and draw tangent to this asymptotic portion that
will be meeting at a point here say
point O then draw an angular bisector to this point that will be meeting the curve at point
A then draw tangent to this line, tangent to this curve through the point A. This is
the tangent.
Now using this information how can we design the system? In this curve itself we can see
different portions. This portion the straight line portion gives the hindered settling,
or if you take the slope of this portion
that will give you the hinder settling velocity Vh. This velocity is very very important for
the design of the sedimentation tank for clarification purpose and this is the transition zone and
this is the compression
zone.
Now we have this point A and we have the tangent and we have the initial height of the settling
column. Now how can we go about it? The area of the clarifier is nothing but Q by Vh that
is the area. So, Q is the
flow rate and Vh is the index settling velocity so we can find out what is the area required.
At the point of intersection of tangent from the hinder settling zone and compression settling
zone draw an angular bisector which meets the curve at A. This has been already discussed.
Now how can we go
ahead? We have to make the mass balance of the entire system. We know that initially
the concentration of the sludge was C0 that means say it is between 2000 to 5000 milligram
per liter and the total height of
the sludge volume is say H0 that means that is the height of the settling column. But
after a particular time what is happening the entire zone will be settling or entire
sludge will be settling and you will be getting a
considerable amount of clear water and entire sludge will be occupying only a small volume
say Hu that we can find out from the system and Cu is the concentration at that time so
how can we find out Hu.
Therefore Hu is equal to C0H0 by Cu. because at any time C0H0 is equal to CuHu. We are
not removing anything from the system the total sludge volume will be remaining as a
constant.
How can we get cu? Here Cu will be your design sludge concentration. So, from this one we
can find out what is the Hu value where Hu is nothing but C0H0 by Cu and Cu is the desired
sludge concentration we
need from the secondary clarifier.
So Hu is available, this is your Hu so you mark it in Hu then draw a horizontal line
through Hu and we will be getting a point where the tangent which has gone through this
A meeting this horizontal line say B.
From B drop a perpendicular that will be meeting your time axis at Tu, so this is the time
required for that much of sludge thickening to take place so you can find out the velocity
of thickening. We have seen
what is the hindered settling velocity and what is area required for the clarification
purpose.
Now we have to find out what is the area required if you want to get a particular amount of
thickening. So the velocity of thickening or thickness is equal to Hu by Tu because
Hu is the high and Tu is the time
available. So velocity is nothing but the distance by time so we get the Vth this is
nothing but velocity of thickening so we can find out what is the area of thickener. The
area of thickener is nothing but Q divided
by velocity of thickening. so we have got two areas; one is A for thickening and another
is A for clarification so two areas are there. You can compare these two areas and if you
want to meet both the purposes
we have to provide the area which is maximum then only we will be able to meet both the
criteria.
Another way of finding the area is continuous flow analysis, because in batch system we
are not considering any under flow. but in any conventional activated sludge process
we take, the sedimentation tank will
be operating in a continuous mode and the sludge will be withdrawing in a continuous
mode so always the effluent will be going from the system and the sludge will be collected
always from the bottom of the
tank so two forces are acting on the sludge. Because of this withdrawal of the sludge there
will be some velocity in which the sludge will be coming down and another one is the
weight of the particle or because
of the gravity force some thickening will be taking place. So if you want to take both
the things into account we can use the flux theory for the design of the secondary sedimentation
tank.
What does this solid flux theory says? Before going into the solid flux theory we
will discuss what solid flux is. Solid flux is nothing but the mass of solids per unit
time passing through a unit area perpendicular to the direction of flow. That means the
amount of particle or mass of the particle passing perpendicular to the cross sectional
area at a given time is known as the solid flux. So, whenever we talk about a sedimentation
tank which is having underflow
constantly then the flux will be because of the under flow velocity as well as because
of gravity. So we have to consider both the things together. So product of solid concentration
and velocity gives you the
solid flux.
Downward velocity is having two components the transport velocity due to the withdrawal
of the sludge and the gravity settling of the solids relative to the water. So transport
velocity is a function of underflow
rate and area of the tank. This is because your sludge withdrawal pipe will be having
much lesser diameter compare to the sludge thickener so the underflow concentration will
be depending upon the underflow
velocity because velocity will be calculated based upon the pipe diameter with which we
are withdrawing the sludge and the area of the clarifier because the flux is nothing
but what is passing through a unit cross
sectional area in the perpendicular direction so if the clarifier area is more then flux
will be less.
The transport velocity vu we can calculate using this formula Vu is equal to Qu divided
by area where Qq is the underflow rate. So solid flux due to underflow we can write like
this; Gu is equal to Vu into Xi that
is nothing but Qu by A into Xi where Xi is the concentration of the sludge whatever is
present in the tank and Qu is the flow rate and A is the area of cross section.
We have already seen that solid flux due to gravity we can calculate using this formula;
Gg is equal to vVg into Xi and Vg is the velocity because of the gravity. So total solid flux
Gt is equal to Gu plus Gg.
I will explain once again. We have a clarifier where the underflow is
also taking place and we know what is the rate at which the sludge is withdrawing from
the sedimentation tank and the sludge is settling down and because of the sludge
weight itself there will be some settling velocity that is known the gravity velocity.
So whenever we consider the sludge settling there are two components; one is because of
the underflow and another one is
because of the gravity. So whenever we consider a particular cross section the total solid
flux is the sum of the solid flux due to the underflow and the solid flux due to the gravity.
Solid flux due to gravity can be calculated using this formula Vg into Xi where Vg is
the velocity due to gravity and Xi is the concentration of the sludge and Gu is nothing
but Vg into Xi and VG is nothing but
the underflow velocity that is Qu by A. Now how can we go around for the design?
We can use the graphical method. There is analytical solution also to find out what
is the area required to achieve a given sludge thickening. So here the y axis gives the solid
flux. Solid flux is nothing but the sum
of the gravity flux and the flux due to underflow. And here we can get the solid concentration.
This line here gives the solid flux due to underflow because V is a constant and Xi keeps
on increasing so you will
be getting a line something similar to this one. And this is the solid flux due to gravity.
So what will happen? Initially it is low then it is increasing then it is decreasing. Why
this particular shape is coming is because initially the concentration of the solids
are relatively low compared to these portions
but the settling velocity or the gravity velocity is high. The flux is nothing but the product
of concentration and the velocity. so here the value will be relatively low but as the
concentration increases the reduction
in the velocity is not so considerable compared to the increase in the concentration so naturally
the product will be high so that will be continuing for certain extent for a particular value
of Xi then afterwards what
will happen is though the concentration of the sludge increases the velocity with which
it is compressing it will be decreasing. The reason is the sludge is so thick so it is
not able to compress it much more. So
the velocity with which it is compressing or with which it is settling will be very
very less so naturally the product of Vi and Xi is coming down as you see in portion and
finally it will be becoming almost
asymptotic like this.
Now we will see how the total flux will be looking like. So this is the flux due to underflow
transport because Vu is remaining as a constant and Xi keeps on increasing so you will be
getting a straight line as
something like this and this is the gravity flux. So the total if you take the gravity
flux plus underflow transport we will be getting this point here and that corresponding to
this distance plus this height is the total
flux so we will be getting a total flux curve as something like this . Therefore, how can
we use this data for the design of a secondary sedimentation tank.
Yoshika suggested an easy graphical solution method for this solid flux using graphical
method. What he has done is he has taken the gravity flux alone by considering the similar
triangle theory. So your gravity
flux is coming as something like this and the flux due to underflow is coming like this.
And if you take the sum of these two things we will be getting the same thing. So here
the triangle was like this and your
gravity flux was like this so take the same triangle this side so you will be getting
underflow transport like this and the gravity flux like this.
Now how to use this information for the design. We want to get an underflow concentration
of Xu1 that means this much is the sludge concentration we need when we withdraw the
sludge from the thickener. So
what we have to do is you have the gravity flux line here so draw a tangent to this gravity
flux line so it will be touching this point and it will be cutting the solid flux line
at some point. For different concentrations
we will be getting different points. For Xu1 you will be getting Gl1 and Xu2 you will be
getting Gl2 and Xu3 you will be getting Gl3. So this Gl1 Gl2 Gl3 is known as the limiting
solid flux that is the maximum flux
we can get for that underflow concentration.
Therefore, using this information we can find out what is the area required for the secondary
sedimentation tank. We know what are the total solids coming to the system. We know what
is the flow rate Q and we
know what is the sludge concentration in the influent so we can find out what is the total
solid loading to the sedimentation tank. Thus, if you know the total solid loading to the
system and unit of the solid flux is
kilogram per hour per meter square that means kilogram per time and area so if you know
total solids loading and the limiting solid flux we can find out the area required.
One interesting thing from this graph is we are drawing a tangent here and where the point
is where this line is meeting the gravity flux curve. If you find out what is the solid
flux corresponding to that one that will
give you the gravity solid flux and this portion will give you the solid flux due to underflow.
This is very very important this is the gravity solid flux and this is the solid flux due
to underflow so we can find out
what is the area required and the area required for the clarifier for the clarification purpose
we can get from the hinder settling velocity.
Here is the summary of this secondary clarifier design. The important objectives are effluent
clarification and the sludge thickening. Conduct laboratory experiments and get necessary data
and based on this do
the design.
Now we have seen now what the nutrient requirement is, what is the sludge production and what
is the loading rate requirement and how much oxygen required and how we can separate the
solids and liquids in
an activated sludge process. Now we have to discuss about how we can supply the oxygen
required for the activated sludge process because unless enough oxygen is supplied to
the system the system
performance will be coming down drastically. We have calculated the total amount of oxygen
required that is nothing but Q into So minus Xe that means the flow rate multiplied by
the BOD removed in the
system minus whatever is converted into the biomass. So what is the requirement of the
aeration?
Oxygen utilization rate of the activated sludge process is much higher compared to the oxygen
whatever is transferring into the system. The rate at which the microorganisms in the
biological reactor consume
oxygen is known as Oxygen utilization rate or it is known as OUR. In any activated sludge
process oxygen utilization rate is always higher than the natural replenishment rate
hence artificial aeration is essential.
We have to meet the oxygen utilization rate in whatever way we can to get the maximum
efficiency so natural aeration will not be able to provide that rate then what is the
other way is we have to go for some
mechanical devices. We will discuss in detail about what are the requirement in oxygen for
different systems of activated sludge process or different modifications of activated sludge
process.
When we talk about extended aeration system we have to supply around 10 milligram per
liter per hour oxygen. That means oxygen consumption rate per time is less in extended aeration
system. In conventional
activated sludge process oxygen utilization rate is 30 milligram per liter per hour and
in high rate activated sludge process the oxygen utilization rate is 100 milligrams
per liter per hour so we should provide the
system which is able to supply this much of oxygen in the given time. For this purpose
we are using aerators.
Aerators are mechanical devices which can supply the require amount of oxygen for an
activated sludge process. Aerators can be of two different types; one is diffused aerators
and another one is mechanical
aerators. We usually go for diffused aerators in plug flow system and mechanical aerators
in conventional activated sludge process where it is a completely tired tank reactor system.
These are the pictures of certain aerators. This is the diffused aerator. We can see that
oxygen is coming out from the diffuser and it is going like this and it is taking a part
something similar to this one. It is going
like this and coming like this so entire area will be getting oxygenated. This shows a surface
aerator. We can see that this is the surface aerator and the water is getting mixed thoroughly
here.
The turbulence available here is much much higher compared to the plug flow or the diffused
aerator. Here well mixing is taking place moreover oxygen transfer is also taking place.
So, in any activated sludge
process aeration tank we provide a series of aerators here, we can see one two three
aerators. So depending upon the oxygen requirement and oxygen transfer rate of these aerators
we can design or we can find
out how many aerators we have to see and depending upon the influence zone of the aerators we
can find out how we should place the aerators. These are also some other pictures of aerators.
Therefore, how can we design the aeration facilities?
The objective of the aeration facility is to provide calculated oxygen demand and to
provide adequate mixing. The D.O concentration in aeration tank; in conventional activated
sludge process we are supposed to
maintain a dissolved oxygen concentration of 0.5 to 1 milligram per liter whereas in
extended aeration system we are supposed to maintain a dissolved oxygen concentration
of 1 to 2 milligram per liter. So your
aeration facility whatever you are going to provide should be able to give this much of
dissolved oxygen concentration in the system.
Now, when we talk about the aerators the aeration itself is very very important and how the
air is getting transferred from the atmosphere to the water. There are many limiting steps
present and there are many
factors affecting the transfer of oxygen from the atmosphere to the wastewater. The most
important things are the turbulence, the temperature, the wastewater characteristics. All these
things are very very
important.
Another one is the saturation limit. If the wastewater oxygen content is very low and
your atmosphere oxygen content is very high and if the concentration gradient available
is very very high then naturally the
oxygen transfer will be very fast. Similarly, if the temperature is low oxygen transfer
will be high and if the temperature is high oxygen transfer will be low. Another parameter
is the wastewater characteristics. In
wastewater there are many compounds or many pollutants present in the wastewater so some
of these compounds are hydrophilic in nature and some are hydrophobic in nature.
Hydrophilic molecule will always have a tendency to be in the liquid or be in the water and
hydrophobic particle will be trying to come out of the system. If the hydrophobic particles
are more in the system what
will happen is it will be forming a thin layer of these particles above the liquid surface
so when that liquid surface layer is there naturally other molecule transfer will be
hindered. So, if the wastewater is having a lot
of solids or lot of hydrophobic solids then naturally the aeration rate will be getting
affected.
The fourth important point is turbulence. If you create more and more turbulence the
oxygen transfer will be more. If the turbulence is very less or the water surface is quiescent
then the oxygen transfer will be
less. We will discuss about this aeration in the next class. Now we will see what are
the things we have discussed today.
We have seen that how we can calculate the oxygen requirements in an activated sludge
process. That is nothing but the BOD consumed in the system but we do not have to supply
oxygen for cell synthesis. So
whatever amount of waste is converted into cell mass that much oxygen requirement we
can detect from the system so total oxygen is the sum of the BOD removed minus 1.42 times
the cell synthesis plus 1.42
times whatever is the cell decayed in the system plus whatever is the oxygen required
for nitrogenous substances. Because, if organic nitrogen or ammonia nitrogen is presented
in the system that will require
some oxygen for the complete oxidation and ammonia will be getting oxidized to nitrate.
So each unit of ammonia requires around 4.7 units of oxygen for the complete removal.
Then we were discussing about what is the nutrient requirement because the microorganisms
requires micronutrients and macronutrients for their growth. In wastewater, most of the
times, these nutrients are
present in plenty so we do not have to supply them externally. But when we talk about some
wastewater which is especially coming from industries they may not be having all these
nutrients now we should know
what is the nutrient requirement for the system. We have also seen that this nutrient requirement
is not a constant; it depends up on the type of or the modified activated sludge process
which we have selected. If
the BSRT is high then BOD is to nitrogen is to phosphorus ratio is high. That means the
nitrogen phosphorus requirement is less but if the BSRT is less it means more and more
cells will be synthesized in the
system so at that we have to give more and more nutrients. That is why high rate activated
sludge requires more nutrients compared to extended aeration system.
Then we have seen how to design a secondary sedimentation tank for an activated sludge
process. It is based upon two concepts or two objectives have to be satisfied. Those
are clarification and sludge
thickening. The area required for the clarification can be calculated based up on hindered settling
velocity and area required for the thickening can be calculated based upon the batch column
studies or by flux
theory. In flux theory we are considering the flux due to underflow as well as gravity
and using the graphical methods we can find out what is the limiting solid flux and for
a system we know what is the sludge
loading per day or per hour so by dividing the limiting flux we will be getting to know
what is the required area.